TDR-480 series
September 26, 2023WDR-60 series
September 27, 2023MW Mean Well Meanwell 960W Slim Three Phase Industrial DIN Rail with PFC Function TDR-960 Series
Features
- Three-Phase 340 ~ 550VAC wide range input (Dual phase operation possible)
- Width only 110mm.
- Built-in active PFC function compliance to BS EN/EN61000-3-2
- High efficiency 94.5% and low power dissipation
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- UL508(industrial control equipment)approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- Current sharing up to 3840W(3+1)
- Built-in DC OK relay contact
- 100% full load burn-in test
- 3 years warranty
Description
TDR-960 is one economical slim 960W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 110mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 3 0 340VAC to 550VAC (Dual Phase operation possible) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. TDR-960 is designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 94.5 %, the entire series can operate at the ambient temperature between -30℃ and 70℃ under air convection. It is equipped with constant current mode for overload protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, IEC 62368-1 CB approved by UL.) make TDR-960 a very competitive power supply solution for industrial applications.
Mean Well Power Supply TDR-960 Series Model Encoding
Mean Well Power Supply TDR-960 Series Data Sheet Download
Specification
MODEL | TDR-960-24 | TDR-960-48 | |
OUTPUT |
DC VOLTAGE | 24V | 48V |
RATED CURRENT | 40A | 20A | |
CURRENT RANGE | 0 ~ 40A | 0 ~ 20A | |
RATED POWER | 960W | 960W | |
RIPPLE & NOISE (max.) Note.2 | 180mVp-p | 250mVp-p | |
VOLTAGE ADJ. RANGE | 24 ~ 28V | 48 ~ 55V | |
VOLTAGE TOLERANCE Note.3 | ±1.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | |
LOAD REGULATION | ±1.0% | ±1.0% | |
SETUP, RISE TIME | 1000ms, 100ms/400VAC 800ms, 100ms/500VAC at full load | ||
HOLD UP TIME (Typ.) | 12ms / 400VAC 14ms / 500VAC at full load | ||
INPUT |
VOLTAGE RANGE Note.4 | Three-Phase 340 ~ 550VAC (Dual phase operation possible) 480 ~ 780VDC | |
FREQUENCY RANGE | 47 ~ 63Hz | ||
POWER FACTOR (Typ.) | PF≧0.88/400VAC PF≧0.86/500VAC at full load | ||
EFFICIENCY (Typ.) | 94% | 94.5% | |
AC CURRENT (Typ.) | 2A/400VAC 1.4A/500VAC | ||
INRUSH CURRENT (Typ.) | COLD START 60A | ||
LEAKAGE CURRENT | <3.5mA / 530VAC | ||
PROTECTION |
OVERLOAD |
105 ~ 130% rated output power | |
Protection type: Constant current limiting, unit will shut down after 3 sec., re-power on to recover | |||
OVER VOLTAGE |
29 ~ 33V | 56 ~ 65V | |
Protection type: Shut down o/p voltage, re-power on to recover | |||
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after temperature goes down | ||
FUNCTION |
DC OK REALY CONTACT RATINGS (max.) | 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load | |
CURRENT SHARING | Please refer to function manual | ||
ENVIRONMENT |
WORKING TEMP. Note.5 | -30 ~ +70℃ (Refer to “Derating Curve”) | |
WORKING HUMIDITY | 20 ~ 95% RH non-condensing | ||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH non-condensing | ||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) | ||
VIBRATION | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | ||
SAFETY & EMC (Note 6) |
SAFETY STANDARDS | UL508, AS/NZS62368.1, BIS IS13252(Part1) (only for 24V), EAC TP TC 004 approved, IEC62368-1 CB approved by SIQ; Design refers to BS EN/EN62368-1 | |
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC | ||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH | ||
EMC EMISSION | Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2, -3, EAC TP TC 020 | ||
EMC IMMUNITY | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2), BS EN/EN61204-3,
heavy industry level, EAC TP TC 020 |
||
OTHERS |
MTBF | 647.1K hrs min. Telcordia SR-332 (Bellcore); 59.5K hrs min. MIL-HDBK-217F (25℃) | |
DIMENSION | 110*125.2*150mm (W*H*D) | ||
PACKING | 2.47Kg; 6pcs/15.8Kg/1.47CUFT |