TDR-240 series
September 26, 2023TDR-960 series
September 26, 2023MW Mean Well Meanwell 480W Slim Three Phase Industrial DIN Rail with PFC Function TDR-480 Series
Features
- Three-Phase 340 ~ 550VAC wide range input (Dual phase operation possible)
- Width only 85.5mm
- Built-in active PFC function compliance to BS EN/EN61000-3-2
- High efficiency 93% and low power dissipation
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- UL508(industrial control equipment)approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- Optional DC OK relay contact
- 3 years warranty
Description
TDR-480 is one economical slim 480W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 85.5mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 3 0 340VAC to 550VAC (Dual Phase operation possible) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. TDR-480 is designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 93 %, the entire series can operate at the ambient temperature between -20℃ and 70℃ under air convection. It is equipped with constant current mode for overload protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, IEC 62368-1 CB approved by UL.) make TDR-480 a very competitive power supply solution for industrial applications.
Mean Well Power Supply TDR-480 Series Model Encoding
Mean Well Power Supply TDR-480 Series Data Sheet Download
Specification
MODEL | TDR-480-24 | TDR-480-48 | ||||
OUTPUT |
DC VOLTAGE | 24V | 48V | |||
RATED CURRENT | 20A | 10A | ||||
CURRENT RANGE | 0 ~ 20A | 0 ~ 10A | ||||
RATED POWER | 480W | 480W | ||||
RIPPLE & NOISE (max.) Note.2 | 150mVp-p | 150mVp-p | ||||
VOLTAGE ADJ. RANGE | 24 ~ 28V | 48 ~ 55V | ||||
VOLTAGE TOLERANCE Note.3 | ±1.0% | ±1.0% | ||||
LINE REGULATION | ±0.5% | ±0.5% | ||||
LOAD REGULATION | ±1.0% | ±1.0% | ||||
SETUP, RISE TIME | 1200ms, 60ms/400VAC 800ms, 60ms/500VAC at full load | |||||
HOLD UP TIME (Typ.) | 20ms / 400VAC 20ms / 500VAC at full load | |||||
INPUT |
VOLTAGE RANGE Note.4 | Three-Phase 340 ~ 550VAC (Dual phase operation possible) 480 ~ 780VDC | ||||
FREQUENCY RANGE | 47 ~ 63Hz | |||||
POWER FACTOR (Typ.) | PF≧0.9/400VAC PF≧0.88/500VAC at full load | |||||
EFFICIENCY (Typ.) | 92.5% | 93% | ||||
AC CURRENT (Typ.) | 0.85A/400VAC 0.7A/500VAC | |||||
INRUSH CURRENT (Typ.) | COLD START 50A | |||||
LEAKAGE CURRENT | <3.5mA / 530VAC | |||||
PROTECTION |
OVERLOAD |
105 ~ 130% rated output power | ||||
Protection type: Constant current limiting, unit will shut down after 3 sec., re-power on to recover | ||||||
OVER VOLTAGE |
29 ~ 33V | 56 ~ 65V | ||||
Protection type: Shut down o/p voltage, re-power on to recover | ||||||
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after temperature goes down | |||||
ENVIRONMENT |
WORKING TEMP. Note.5 | -30 ~ +70℃ (Refer to “Derating Curve”) | ||||
WORKING HUMIDITY | 20 ~ 95% RH non-condensing | |||||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH | |||||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) | |||||
VIBRATION | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | |||||
SAFETY & EMC (Note 4) |
SAFETY STANDARDS | UL508, IEC62368-1, UL 62368-1, AS/NZS 62368.1, BIS IS13252(Part1) (only for 24V), EAC TP TC 004 approved,
Design refers to BS EN/EN62368-1 |
||||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK(optional):0.5KVAC | |||||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH | |||||
EMC EMISSION |
Parameter | Standard | Test Level / Note | |||
Conducted | BS EN/EN55032(CISPR32) / BS EN/EN61204-3 | Class B | ||||
Radiated | BS EN/EN55032(CISPR32) / BS EN/EN61204-3 | Class B | ||||
Harmonic Current | BS EN/EN61000-3-2 | Class A | ||||
Voltage Flicker | BS EN/EN61000-3-3 | —– | ||||
EMC IMMUNITY |
BS EN/EN55035 , BS EN/EN61204-3 | |||||
Parameter | Standard | Test Level / Note | ||||
ESD | BS EN/EN61000-4-2 | Level 4, 15KV air ; Level 4, 8KV contact | ||||
Radiated Field | BS EN/EN61000-4-3 | Level 3 | ||||
EFT / Burst | BS EN/EN61000-4-4 | Level 3 | ||||
Surge | BS EN/EN61000-4-5 | Level 4, 2KV / Line-Line, Level 4, 4KV/ Line-Earth | ||||
Conducted | BS EN/EN61000-4-6 | Level 3 | ||||
Magnetic Field | BS EN/EN61000-4-8 | Level 4 | ||||
Voltage Dips and Interruptions |
BS EN/EN61000-4-11 |
>95% dip 0.5 periods, 30% dip 25
periods> 95% interruptions 250 periods |
||||
OTHERS |
MTBF | 1174.0K hrs min. Telcordia SR-332(Bellcore); 108.3K hrs min. MIL-HDBK-217F (25℃) | ||||
DIMENSION | 85.5*125.2*128.5mm (W*H*D) | |||||
PACKING | 1.51Kg; 8pcs/13Kg/1.16CUFT |