HRPG-600 series
June 26, 2023HRP-150N3 series
June 27, 2023MW Mean Well Meanwell 1000W Single Output with PFC Fucntion Switching Power Supply HRPG-1000 series
Features
- Universal AC input / Full range
- Built-in active PFC function, PF>0.95
- High efficiency up to 94%
- Withstand 300VAC surge input for 5 seconds
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Built-in cooling fan ON-OFF control
- Current sharing up to 4000W (3+1)
- Built-in DC OK signal
- Built-in remote ON-OFF control
- Standby [email protected]
- Built-in remote sense function
- No load power consumption<0.75W
- 5 years warranty
Mean Well Enclosed Switching Power Supply HRPG-1000 Series Data Sheet Download
Description
The Mean Well enclosed switching power supply HRPG-1000 series is a family of high-reliability, high-performance AC/DC power supplies designed for industrial and medical applications. These power supplies feature a universal AC input range of 85-264VAC, and are available in a range of output voltages, 12VDC (Model N0.: HRPG-1000-12), 15VDC (Model N0.: HRPG-1000-15), 24VDC (Model N0.: HRPG-1000-24), and 48VDC (Model N0.: HRPG-1000-48).
The Mean Well power supply HRPG-1000 series is highly efficient, with a typical efficiency of up to 94%, and is fully protected against overvoltage, overcurrent, and short-circuit conditions. These power supplies are built with high-quality components and are designed to operate over a wide temperature range, from -40°C to +70°C.
The MEAN WELL SMPS with PFC function HRPG-1000 series is designed for high reliability, with a mean time between failures (MTBF) of up to 500,000 hours. These power supplies are also equipped with a built-in active PFC function, which helps to reduce harmonic distortion and improve power factor.
Overall, the Mean Well single output switching power supply HRPG-1000 series is a high-performance, reliable, and versatile power supply solution for a wide range of industrial and medical applications.
Mean Well Enclosed Switching Power Supply HRPG-1000 Series Model Encoding
Specification
MODEL | HRPG-1000-12 | HRPG-1000-15 | HRPG-1000-24 | HRPG-1000-48 | |||
OUTPUT |
DC VOLTAGE | 12V | 15V | 24V | 48V | ||
RATED CURRENT | 80A | 64A | 42A | 21A | |||
CURRENT RANGE | 0 ~ 80A | 0 ~ 64A | 0 ~ 42A | 0 ~ 21A | |||
RATED POWER | 960W (max. 1000W for 3 sec.) | 960W (max. 1000W for 3 sec.) | 1008W | 1008W | |||
RIPPLE & NOISE (max.) Note.2 | 150mVp-p | 150mVp-p | 200mVp-p | 250mVp-p | |||
VOLTAGE ADJ. RANGE | 11 ~ 14V | 14 ~ 17V | 22 ~ 28V | 46 ~ 56V | |||
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.5% | ±1.0% | ±1.0% | |||
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | ±0.5% | |||
LOAD REGULATION | ±2.0% | ±1.5% | ±0.5% | ±0.5% | |||
SETUP, RISE TIME | 1000ms, 50ms/230VAC 2000ms, 50ms/115VAC at full load | ||||||
HOLD UP TIME (Typ.) | 16ms/230VAC 16ms/115VAC at full load | ||||||
INPUT |
VOLTAGE RANGE Note.4 | 90 ~ 264VAC (300VAC for 5 sec.) 127 ~ 370VDC | |||||
FREQUENCY RANGE | 47 ~ 63Hz | ||||||
POWER FACTOR (Typ.) | PF>0.95/230VAC PF>0.99/115VAC at full load | ||||||
EFFICIENCY (Typ.) | 91.5% | 92% | 93% | 94% | |||
AC CURRENT (Typ.) | 8.5A/115VAC 5A/230VAC | ||||||
INRUSH CURRENT (Typ.) | 25A/115VAC 40A/230VAC | ||||||
LEAKAGE CURRENT | <1.2mA / 240VAC | ||||||
PROTECTION |
OVERLOAD | 105 ~ 135% rated output power | |||||
Protection type: Constant current limiting, recovers automatically after fault condition is removed | |||||||
OVER VOLTAGE | 14.5 ~ 16.5V | 18.2 ~ 20.6V | 29 ~ 33V | 58 ~ 65V | |||
Protection type: Shut down o/p voltage, re-power on to recover | |||||||
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after temperature goes down | ||||||
FUNCTION |
CURRENT SHARING | Up to 4000W or (3+1) units. Please refer to the Function Manual. | |||||
REMOTE ON-OFF CONTROL | Power ON: short; Power OFF: open. Please refer to the Function Manual. | ||||||
REMOTE SENSE | Compensate voltage drop on the load wiring up to 0.5V. Please refer to the Function Manual. | ||||||
DC-OK SIGNAL | The TTL signal out, PSU turn on = 3.3 ~ 5.6V; PSU turn off = 0 ~ 1V. Please refer to the Function Manual. | ||||||
5V STANDBY | 5VSB: [email protected] ; tolerance±5%, ripple: 50mVp-p(max.) | ||||||
FAN CONTROL | Fan on/off by NTC(RT50) or 30% load min. | ||||||
ENVIRONMENT |
WORKING TEMP. | -40 ~ +70℃ (Refer to “Derating Curve”) | |||||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | ||||||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH non-condensing | ||||||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) | ||||||
VIBRATION | 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes | ||||||
SAFETY & EMC (Note 7) |
SAFETY STANDARDS | UL62368-1, CAN/CSA C22.2 No. 62368-1, TUV BS EN/EN62368-1, AS/NZS62368.1, EAC TP TC 004 approved | |||||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | ||||||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH | ||||||
EMC EMISSION |
Parameter | Standard | Test Level / Note | ||||
Conducted | BS EN/EN55032 (CISPR32) | Class B | |||||
Radiated | BS EN/EN55032 (CISPR32) | Class B | |||||
Harmonic Current | BS EN/EN61000-3-2 | Class A | |||||
Voltage Flicker | BS EN/EN61000-3-3 | —– | |||||
EMC IMMUNITY |
BS EN/EN55035, BS EN/EN61000-6-2 | ||||||
Parameter | Standard | Test Level / Note | |||||
ESD | BS EN/EN61000-4-2 | Level 3, 8KV air ; Level 2, 4KV contact | |||||
Radiated | BS EN/EN61000-4-3 | Level 3 | |||||
EFT / Burst | BS EN/EN61000-4-4 | Level 3 | |||||
Surge | BS EN/EN61000-4-5 | Level 4, 2KV/Line-Line 4KV/Line-Earth | |||||
Conducted | BS EN/EN61000-4-6 | Level 3 | |||||
Magnetic Field | BS EN/EN61000-4-8 | Level 4 | |||||
Voltage Dips and Interruptions | BS EN/EN61000-4-11 | >95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods |
|||||
OTHERS |
MTBF | 862.1K hrs min. Telcordia SR-332 (Bellcore); 105.9K hrs min. MIL-HDBK-217F (25℃) | |||||
DIMENSION | 218*105*63.5mm (L*W*H) | ||||||
PACKING | 1.53Kg; 8pcs/13.3Kg/1.34CUFT |
Application
- Industrial automation machinery
- Industrial control system
- Mechanical and electrical equipment
- Electronic instruments, equipments or apparatus